耐火試驗(yàn)中電纜橋架的耐火時(shí)間是如何規(guī)定的?
根據(jù) GB 29415—2013《耐火電纜槽盒》,電纜橋架耐火時(shí)間分為 4 個(gè)等級(jí):
According to GB 29415-2013 "Fire resistant Cable Tray Boxes", the fire resistance time of cable trays is divided into four levels:
F1:大于等于 90 分鐘。
F1: Greater than or equal to 90 minutes.
F2:大于等于 60 分鐘。
F2: Greater than or equal to 60 minutes.
F3:大于等于 45 分鐘。
F3: Greater than or equal to 45 minutes.
F4:大于等于 30 分鐘。
F4: Greater than or equal to 30 minutes.
另外,也有資料將電纜橋架的耐火等級(jí)分為 NI、NII、NIII 三個(gè)等級(jí),其中 NI 等級(jí)耐火時(shí)間大于等于 60 分鐘,NII 等級(jí)大于等于 45 分鐘,NIII 等級(jí)大于等于 30 分鐘。
In addition, there are also materials that classify the fire resistance level of cable trays into three levels: NI, NII, and NIII. Among them, the fire resistance time of NI level is greater than or equal to 60 minutes, NII level is greater than or equal to 45 minutes, and NIII level is greater than or equal to 30 minutes.
不同使用環(huán)境對(duì)防火橋架的耐火時(shí)間要求有所不同,如地下車庫等對(duì)防火有特別要求的地段,防火橋架耐火時(shí)間要求大于 1 小時(shí)。在實(shí)際應(yīng)用中,應(yīng)根據(jù)具體的工程需求和相關(guān)規(guī)范來選擇合適耐火時(shí)間的電纜橋架。
The fire resistance time requirements for fire-resistant cable trays vary depending on the usage environment. For example, in underground garages and other areas with special fire protection requirements, the fire resistance time of fire-resistant cable trays should be greater than 1 hour. In practical applications, cable trays with appropriate fire resistance time should be selected based on specific engineering requirements and relevant specifications.
下一篇:耐火試驗(yàn)后電纜橋架的性能和質(zhì)量如何評(píng)估?
相關(guān)文章 / Recommended news
- 山東電纜橋架:金屬線槽橋架安裝工藝要點(diǎn)!
- 濟(jì)南電纜橋架:電纜橋架常用的安裝方式及安裝單價(jià)分享
- 山東電纜橋架:設(shè)計(jì)施工時(shí)金屬橋架怎么接地?
- 濟(jì)南電纜橋架:橋架外形尺寸允許偏差要求
- 山東電纜橋架:一文讀懂國標(biāo)電纜橋架厚度規(guī)定
- 濟(jì)南電纜橋架:關(guān)于電纜橋架接地問題應(yīng)對(duì)措施
- 山東電纜橋架:槽式橋架與托盤式電纜橋架的區(qū)別
- 山東電纜橋架:槽式橋架與托盤式電纜橋架的區(qū)別
- 濟(jì)南電纜橋架:電纜橋架的分類、材質(zhì)、組合結(jié)構(gòu)和產(chǎn)品介紹
- 山東電纜橋架的接地非常重要及接地注意事項(xiàng)